Gas Insulated Substation (GIS) Advantages - Disadvantages

Updated on January 2, 2014
Indoor Gas Insulated Substation
Indoor Gas Insulated Substation

Introduction

Gas Insulated Substation uses sulfur hexafluoride (SF6) gas which has a superior dielectric properties used at moderate pressure for phase to phase and phase to ground insulation. In Gas Insulated Substation the high-voltage conductors, circuit breaker interrupters, switches, current transformers, voltage transformers and lightning arresters are encapsulated in SF6 gas inside grounded metal enclosures.

Where and Why Gas Insualted Substations are Used

Gas Insulated Substations are used where there is space for providing the substation is expensive in large cities and towns. In normal substation the clearances between the phase to phase and phase to ground is very large. Due to this, large space is required for the normal or Air Insulated Substation (AIS). But the dielectric strength of SF6 gas is higher compared to the air, the clearances required for phase to phase and phase to ground for all equipments are quite lower. Hence, the overall size of each equipment and the complete substation is reduced to about 10% of the conventional air insulated substation.

Locations where Gas Insulated Substation is preferred:

  • Large cities and towns
  • Underground stations
  • Highly polluted and saline environment Indoor GIS occupies very little space
  • Substations and power stations located Off shore
  • Mountains and valley regions

Explaination:

The SF6 Gas Insulated Substation (GIS) contains the same compartments as in the conventional outdoor substations. All the live parts are enclosed in metal housings filled with SF6 gas. The live parts are supported on cast resin insulators. Some of the insulators are designed as barriers between neighboring modules such that the gas does not pass through them. The entire installation is sub divided into compartments which are gas tight with respect to each other. Thereby the gas monitoring system of each compartment can be independent and simpler.

The enclosures are of non magnetic materials such as aluminum or stainless steel and are earthed. The gas tightness is provided with static ‘O’ seals placed between the machined flanges. The ‘O’- rings are placed in the grooves such that after assembly, the ‘O’-rings are get squeezed by about 20%. Quality of the materials, dimension of grooves and ‘O’-seals are important to ensure gas tight performance of Gas Insulated Substation.

Gas Insulated Substation has gas monitoring system. Gas inside each compartment should have a pressure of about 3kg/cm2.The gas density in each compartment is monitored. If the pressure drops slightly, the gas is automatically trapped up. With further gas leakage, the low pressure alarm is sounded or automatic tripping or lock-out occurs.

Merits of SF6 Gas Insulated Substation:

Safe:

Gas insulated Substations are very safe and operating personnel are protected by the earthed metal enclosures. While the Substation in operating condition the Operating personnel can touch the compartment.

Reliable:

The complete enclosure of all live parts guards against any impairment of the insulation system.

Space Saving:

SF6 switchgear installations take up only 10% of the space required for the conventional installations.

Economical:

Initial high investment is required for installation but the cost can be comparable for the less maintenance, reliable, safe operation against conventional substation.

Maintenance Free:

An extremely careful selection of materials, an expedient design and a high standard of manufacturing quality assure long service life with practically no maintenance requirement.

Low Weight:

Low weight due to aluminum enclosure, corresponds to low cost foundations and buildings.

Shop assembled:

Quick site assembly ensured by extensive pre assembly and testing of complete feeders or large units in the factory.

Demerits Of Gas Insulated Substation:

  • Cost is higher compared to Air Insulated Substation or conventional substation.
  • Procurement of SF6 gas and supply of gas to the site is problematic
  • Normally this type of substations are indoor type and requires separate building
  • Maintaining Cleanliness is very important. Dust or moisture inside the compartment causes the flash overs
  • When fault occurs internally, the outage period will be very long. The damage effect will also be severe.

Comments

    0 of 8192 characters used
    Post Comment

    • profile image

      Narayanamoorthi 

      3 years ago

      i need the GIS specifications...for example how much of pressure used in CB,and how much of pressure used in Isolator....etc...

    • profile image

      Pharmf659 

      4 years ago

      Hello! eakcake interesting eakcake site! I'm really like it! Very, very eakcake good!

    • profile image

      sabuj 

      5 years ago

      what is the minimum distance between the control panel & g.i.s. circuite breaker?

    • profile image

      Balki 

      5 years ago

      what is the minimum area required for the 33 kv GIS substation and compare the cost between normal AIS Substation and GIS sub station

    • profile image

      bhagwat 

      5 years ago

      this is good information i have used in ppts

      thanks

    • profile image

      martinnitsim 

      5 years ago

      hello there dennis i shouldn't give it out but i think this is the site

      and some info , there very helpful ,say netsims said you would sort him out

    • profile image

      ajay krishna 

      6 years ago

      good informTION

    • profile image

      sai 

      6 years ago

      i need the dimensions of the insulating flange

    • profile image

      Gami Red 

      6 years ago

      What causes explosion (pressure relief valve actuation) in the modules? Is it flashover alone due to dust/moisture or something else? Is a failure of the CVT a possibility? How is this determined after such incident? Thank you!

    • profile image

      irfan. 

      6 years ago

      thnkz for the....why these are not implemented in india....

    • profile image

      prosper 

      6 years ago

      this is a good and reliable information.thanks

    • kiran111 profile imageAUTHOR

      kiran111 

      7 years ago

      Dear Tivayki,

      Flash over happens when the SF6 gas pressure in the module (compartment) is not maintained, when the gas inside the module is not clean ( this happens due to the leakage in the modules purity of sf6 comes down results in flashovers)

    • profile image

      S.Tivayki 

      7 years ago

      thank you for this hub. could you please specify the possible flash over due to the dust and moisture inside GIS. if the system is isolated how can it flash over?

      thx.

    • profile image

      m.chaithanya 

      7 years ago

      what is the use of gas insulated substation

    • profile image

      g.sankar 

      7 years ago

      why gas circuit breker has themost efficient

    working

    This website uses cookies

    As a user in the EEA, your approval is needed on a few things. To provide a better website experience, hubpages.com uses cookies (and other similar technologies) and may collect, process, and share personal data. Please choose which areas of our service you consent to our doing so.

    For more information on managing or withdrawing consents and how we handle data, visit our Privacy Policy at: https://hubpages.com/privacy-policy#gdpr

    Show Details
    Necessary
    HubPages Device IDThis is used to identify particular browsers or devices when the access the service, and is used for security reasons.
    LoginThis is necessary to sign in to the HubPages Service.
    Google RecaptchaThis is used to prevent bots and spam. (Privacy Policy)
    AkismetThis is used to detect comment spam. (Privacy Policy)
    HubPages Google AnalyticsThis is used to provide data on traffic to our website, all personally identifyable data is anonymized. (Privacy Policy)
    HubPages Traffic PixelThis is used to collect data on traffic to articles and other pages on our site. Unless you are signed in to a HubPages account, all personally identifiable information is anonymized.
    Amazon Web ServicesThis is a cloud services platform that we used to host our service. (Privacy Policy)
    CloudflareThis is a cloud CDN service that we use to efficiently deliver files required for our service to operate such as javascript, cascading style sheets, images, and videos. (Privacy Policy)
    Google Hosted LibrariesJavascript software libraries such as jQuery are loaded at endpoints on the googleapis.com or gstatic.com domains, for performance and efficiency reasons. (Privacy Policy)
    Features
    Google Custom SearchThis is feature allows you to search the site. (Privacy Policy)
    Google MapsSome articles have Google Maps embedded in them. (Privacy Policy)
    Google ChartsThis is used to display charts and graphs on articles and the author center. (Privacy Policy)
    Google AdSense Host APIThis service allows you to sign up for or associate a Google AdSense account with HubPages, so that you can earn money from ads on your articles. No data is shared unless you engage with this feature. (Privacy Policy)
    Google YouTubeSome articles have YouTube videos embedded in them. (Privacy Policy)
    VimeoSome articles have Vimeo videos embedded in them. (Privacy Policy)
    PaypalThis is used for a registered author who enrolls in the HubPages Earnings program and requests to be paid via PayPal. No data is shared with Paypal unless you engage with this feature. (Privacy Policy)
    Facebook LoginYou can use this to streamline signing up for, or signing in to your Hubpages account. No data is shared with Facebook unless you engage with this feature. (Privacy Policy)
    MavenThis supports the Maven widget and search functionality. (Privacy Policy)
    Marketing
    Google AdSenseThis is an ad network. (Privacy Policy)
    Google DoubleClickGoogle provides ad serving technology and runs an ad network. (Privacy Policy)
    Index ExchangeThis is an ad network. (Privacy Policy)
    SovrnThis is an ad network. (Privacy Policy)
    Facebook AdsThis is an ad network. (Privacy Policy)
    Amazon Unified Ad MarketplaceThis is an ad network. (Privacy Policy)
    AppNexusThis is an ad network. (Privacy Policy)
    OpenxThis is an ad network. (Privacy Policy)
    Rubicon ProjectThis is an ad network. (Privacy Policy)
    TripleLiftThis is an ad network. (Privacy Policy)
    Say MediaWe partner with Say Media to deliver ad campaigns on our sites. (Privacy Policy)
    Remarketing PixelsWe may use remarketing pixels from advertising networks such as Google AdWords, Bing Ads, and Facebook in order to advertise the HubPages Service to people that have visited our sites.
    Conversion Tracking PixelsWe may use conversion tracking pixels from advertising networks such as Google AdWords, Bing Ads, and Facebook in order to identify when an advertisement has successfully resulted in the desired action, such as signing up for the HubPages Service or publishing an article on the HubPages Service.
    Statistics
    Author Google AnalyticsThis is used to provide traffic data and reports to the authors of articles on the HubPages Service. (Privacy Policy)
    ComscoreComScore is a media measurement and analytics company providing marketing data and analytics to enterprises, media and advertising agencies, and publishers. Non-consent will result in ComScore only processing obfuscated personal data. (Privacy Policy)
    Amazon Tracking PixelSome articles display amazon products as part of the Amazon Affiliate program, this pixel provides traffic statistics for those products (Privacy Policy)